Woodpecker Cosyman Pellet Boiler Maintenance Keighley (update)

Keighley
BD20 5AN

Description of work:

Woodpecker Cosyman 25 kW pellet boiler annual maintenance 2017.
Fire chamber cleaning
Fire chamber back board replacement
Fire chamber bottom board replacement
Fire chamber door board replacement
Fire chamber door bolt replacement using stainless steel threaded rods and nuts
Photo probe cleaning
Materials used:
Vermiculite fire chamber back board 21 ½” x 13 ½” x 1” (545 x 350 x 25)
Vermiculite fire chamber bottom board
Vermiculite fire chamber door board 12 x 13 ½” x 3/4” (300 x 350 x 20)
Replacement control board backup battery CR2032

Cosyman boiler fire chamber
Cosyman boiler fire chamber

Cosyman boiler secondary heat exchanger
Secondary heat exchanger

Cosyman boiler fire tube
Fire tube needs to be replaced

Cosyman boiler fire tube
Fire tube: the old one and the new one.

After 15 years of operation the small backup battery in the main controller board broke. There was an error code 9 and the boiler didn’t start. After starting the ignition process immediately stopped and started extinguishing. Sometimes the backup battery must be replaced live, otherwise the controller forgets every setting. We did it the following way:

  • Stopped the boiler, letting it to do the extinguishing procedure.
  • De-energised the boiler with the main fuse
  • Removed the cover of the main controller board
    The battery on the panel
    The battery on the panel
  • Reenergised the boiler and waited to stop fully
  • Carefully replaced the battery
  • The replacement battery
    The replacement battery

  • Checked if the boiler could start as it should
  • Put back all the covers

Lesson learned: the battery should be replaced after 10 years even if it still works.